Enter a concrete wall, the soil it holds back and the soil it stands on. Rischio’s engine works out the earth pressure behind the wall and checks it for sliding, bearing and the eccentricity of the resultant, as the studio does. It’s free and needs no account.
Calculator · Rischio's engine · retaining wall stability
These data give no result: check the values.
Rischio's engine calculated this. In the studio you keep the model, change it on the drawing and get the calculation report, every step shown.
Start freeThis calculator is offered for information and technical support. It doesn't replace professional judgment or the reviews due, and its use is the user's responsibility.
How it calculates
The calculator checks a one-metre slice of the wall as a rigid body: its own weight and the soil’s against the push of the backfill. It works as AASHTO LRFD’s Article 11.6 does, with factors of safety in place of load and resistance factors.
The backfill pushes with Rankine’s active pressure on the virtual back, the vertical plane through the back edge of the base. The soil between the wall and that plane counts as part of the wall’s weight. With the backfill’s surface sloping at , the active coefficient is
and the pressure at each depth is , parallel to the surface. The backfill is taken as a granular fill without cohesion, as AASHTO takes it. The horizontal part of the thrust pushes the wall over; its vertical part bears down on the heel and helps hold it.
Below the water table, the backfill pushes with its submerged weight and the water adds its own thrust, , plus an uplift on the base. The soil in front of the toe isn’t counted as a resistance (AASHTO 11.6.3.5 lets the design leave it out), so the wall stands on its base alone.
With those forces, the three checks:
| Check | What it compares | Minimum |
|---|---|---|
| Eccentricity | at most | |
| Sliding on the base | 1.5 | |
| Bearing | 3 |
The eccentricity replaces a factor of safety against overturning, as in AASHTO (11.6.3.3). AASHTO keeps the factored resultant within the middle two-thirds of the base on soil; the calculator asks for the middle third under the unfactored loads, the usual limit in FHWA’s practice. Sliding takes the friction of concrete cast on the foundation soil, (AASHTO Eq. 10.6.3.4-2). For bearing, the load spreads uniformly over the effective width , , after Meyerhof, and is AASHTO’s bearing resistance equation on with the load’s inclination (the bearing capacity calculator shows that equation on its own). The base’s pressures at its edges, , are drawn under it. The minimums are the calculator’s, the usual ones for retaining walls in US practice (FHWA GEC 6).
Each step, with its equations, is in the docs: earth pressure, stability and bearing capacity.
How to use it
- Pick the wall: a cantilever wall (a stem on a footing) or a gravity wall (one block of concrete).
- Give its dimensions. For a cantilever, the height from the bottom of the footing to the crest, the base width, the toe’s length, the footing’s thickness and the stem’s width at the top and at the base. For a gravity wall, its height, its base and crest widths and how much its back leans.
- Give how deep the base sits below the ground in front of the toe.
- Describe the backfill: its unit weight, friction angle, the slope of its surface and any surcharge on it. Turn on the water table if the backfill isn’t drained.
- Describe the foundation soil the wall stands on.
The results show the three checks, the wall drawn with the earth pressure behind it and the pressure under its base, and a table with every force and moment. Restore the example brings back the studio’s template, a 6 m cantilever wall: m against m, and factors of safety of 1.82 against sliding and 4.64 against bearing. To keep the wall, add strata, try a gabion wall or get a calculation report with every step, design it in Rischio’s retaining wall tool.
Frequently asked questions
How do you calculate the stability of a retaining wall?
Work out the forces on a one-metre slice: the weights of the wall and of the soil over its heel, and the earth and water pressure behind it. Then check that the resultant crosses the base within its middle third, so the wall doesn’t tip, that it doesn’t slide on its base and that it doesn’t overload the soil under it.
What factor of safety does a retaining wall need?
The usual minimums are 1.5 against sliding and 3 against bearing capacity failure, the defaults this calculator uses, with the resultant within the middle third of the base. Some codes and owners ask for other values, so the ones that apply to a project come from its specifications. AASHTO LRFD uses load and resistance factors in their place.
What is the middle third rule for retaining walls?
The resultant of all the forces on the wall should cross the base within its middle third, which means an eccentricity of at most . Then the whole base presses on the soil. Past that point, turns negative and the heel side of the base starts to lift off. AASHTO LRFD judges overturning by the eccentricity too, with factored loads and the middle two-thirds on soil.
How thick does a retaining wall need to be?
The checks decide it, but there are usual first sizes. For a cantilever wall, a base about 0.5 to 0.7 times the height, a footing about a tenth of the height thick, and a stem at least 0.3 m (12 in) wide at the top, wider at its base. A gravity wall needs more width, because its own weight is what holds it.
What doesn’t this calculator check?
It checks the wall’s external stability. The structural design of the stem and the footing (their bending, shear and reinforcement), the global stability of the slope around the wall and its settlement are separate checks.