A retaining wall's base as a strip footing under an eccentric, inclined load: AASHTO's bearing equation on the effective width, the strata below.

Rischio checks the base of the wall as a strip footing, under the resultant of the forces in Stability. AASHTO’s 11.6.3.2 sends a wall’s bearing on soil to the footing’s, and the base goes through the footing’s own code; this page covers what is particular to the wall, and the rest is in Footings › Bearing capacity.

The base as a strip footing

The base is a strip footing of width BB at depth DfD_f, the ground in front of the toe, under ΣV\Sigma V at an eccentricity ee and ΣH\Sigma H. ΣV\Sigma V takes what bears on the base over the heel, which sliding and the eccentricity leave out: a surcharge there (AASHTO C11.5.6, Fig. C11.5.6-3) and each line load within the base’s width (FHWA NHI-06-089, §10.5.3). A dead one is always there, as ES under AASHTO; a live one comes and goes on its own (3.4.1), and the bearing takes it in or out, whichever is worse, its inertia with it under an earthquake. Its nominal resistance qnq_n comes from AASHTO’s Eq. 10.6.3.1.2a-1, in free mode as under AASHTO, on the effective width B′=B−2eB' = B - 2e, with the cc and ϕ\phi of the stratum the base rests on:

qn=cNcic+γDfNqdqiqCwq+12γB′NγiγCwγq_n = c N_c i_c + \gamma D_f N_q d_q i_q C_{wq} + \tfrac{1}{2} \gamma B' N_\gamma i_\gamma C_{w\gamma}

The shape factors are 1 for a strip. NcN_c, NqN_q and NγN_\gamma, the depth factor dqd_q, the inclination factors with ΣH\Sigma H and ΣV\Sigma V, and the water factors are the footing’s, in AASHTO’s equation. dqd_q, at most 1.4, counts the shear of the soil in front of the toe, over the base, only where Soil in front stays is checked: that soil stays through the wall’s life, with no scour, excavation or trench to take it, and isn’t weaker than the stratum below (10.6.3.1.2a). Unchecked, the default, dq=1d_q = 1, as for a toe that may be dug out or scoured. Where Vesic’s rigidity index of the stratum B/2B/2 below the base says it can fail in local or punching shear, it takes c∗c^* and ϕ∗\phi^*, as a footing does.

The factor of safety weighs qnq_n against the equivalent uniform pressure on that width, as for a footing on soil:

qeq=ΣVB′,FS=qnqeqq_{eq} = \frac{\Sigma V}{B'}, \qquad FS = \frac{q_n}{q_{eq}}

UFS 3-220-20 (§4-5.1.4) and FHWA NHI-06-089 (Fig. 10-17, after NAVFAC 1986b) take the uniform pressure for a wall on soil: a soil yields under the toe and the failure takes the whole effective width, which qnq_n already counts. Under AASHTO the check is ϕbqn\phi_b q_n, ϕb=0.55\phi_b = 0.55, against the factored V/(B−2e)V/(B - 2e) (AASHTO LRFD).

With e≥B/2e \ge B/2 the resultant leaves the base: there is no contact pressure, and the factor of safety is 0.

The strata below

Like a footing, the base sees the strata below it: a weaker stratum within the critical depth (a softer clay under a clay, past it too, to the cap of its NmN_m) lowers qnq_n by AASHTO’s 10.6.3.1.2d to f (Footings › Two strata), under an earthquake too. A stronger stratum below and rock under the strata aren’t counted, the conservative side.

Settlement

Where its foundation strata have their moduli or their consolidation, the base also settles as a strip footing at Service I, by the footing’s own methods (AASHTO 11.6.2.2 sends it to 10.6.2.4; Footings › Settlement).