Bearing capacity
Eccentricity and effective area, contact pressure, the two bearing equations, local shear, a weaker stratum below, the factor of safety and sliding.
This page follows the load from where it acts on the base to the factor of safety; the units, conventions and assumptions are in Method and assumptions.
Eccentricity and effective area
The moments move the resultant off centre by and . The bearing capacity uses Meyerhof’s effective area, the part of the base centred on the resultant (AASHTO 10.6.1.3). Its sides are and : is the shorter of them and the longer, whichever the user called the width. A strip has only . The plan view draws the effective area once the model is calculated.
A circular footing is taken as the square of the same area, of side (AASHTO C10.6.1.3), in both equations; its contact pressure is on the circle, . Its load is centred, so it has no eccentricity checks; a horizontal load still inclines it.
Contact pressure
The contact pressure is linear over the whole base, with and at opposite corners (at the edges, for a strip) and , or per metre for a strip. Once exceeds 1, is negative: that corner would be in tension, which the soil can’t take, so it lifts off. Rischio doesn’t redistribute the pressure; it keeps the negative value to show how far out the load is. With one eccentricity this is the middle third: or makes negative and fails its eccentricity check.
When or the resultant falls outside the base and the footing overturns: there is no contact pressure or , and the bearing check gives , which fails any limit.
Ultimate bearing capacity
AASHTO’s 10.6.3.1.2a asks for the nominal resistance by “accepted soil mechanics theories”, and a footing can take either of two equations, under Methods. Left as it is, it takes its design code’s: the general bearing capacity equation in free mode, and AASHTO’s Eq. 10.6.3.1.2a-1 under AASHTO. Both take the and of the stratum the base rests on, on the effective area, and the same factors , and . The base of a retaining wall and the block of an MSE wall take AASHTO’s always.
Bearing capacity factors
Reissner, Prandtl and Vesic, the closed forms that AASHTO’s Table 10.6.3.1.2a-1 rounds; with , the undrained case, , and :
The general equation, free mode’s default
Meyerhof’s general equation, with the factors as the textbooks give them:
The overburden is the effective vertical stress at the base: the weight of the strata above, with above the water table and below, less the pore pressure. is the thickness-weighted average between and , with above the water table and below. With one stratum these are the three classic cases: the water table above the base, within below it, or deeper.
De Beer’s shape factors take , and for a strip all three are 1:
Hansen’s depth factors take the full width , the shorter side of the base, for :
With , and . For , is replaced by , in radians.
The inclination factors are Meyerhof’s, and Hanna and Meyerhof’s, with the inclination of the load in degrees, the same whichever way the load leans. Once the term is gone, (the square would bring it back); with , :
AASHTO’s equation, the default under AASHTO
AASHTO’s Eq. 10.6.3.1.2a-1, with its own factors and the water in and :
in the second term is the moist unit weight above the base, averaged by thickness, and in the third the bearing stratum’s.
- Shape (Table 10.6.3.1.2a-3): with , , and ; with , and .
- Depth (Table 10.6.3.1.2a-4): , at most 1.4, and 1 where a stratum above the base is weaker than the one it rests on, as the table’s note asks, the two compared by their own friction angles even where local shear reduces the base’s; with , . It counts the shear of the soil over the base, so it’s taken only where Soil over the base stays is checked: that soil stays through the structure’s life, with no scour, excavation or trench to take it (10.6.3.1.2a). Unchecked, the default, . The same holds in the pairing with a weaker stratum below (Two strata); the general equation keeps its own depth factors.
- Inclination (Eqs. 10.6.3.1.2a-5 to -9), the load along : , and , with ; with , and . Where the load leans past what the soil takes, the three terms sum below zero (at , leaves ), and is 0: a resistance below zero is none.
- Water (Table 10.6.3.1.2a-2): is 0.5 with the water table at the ground and 1.0 at the base or deeper; is 0.5 at the base or higher and 1.0 from below it. Between the table’s rows both vary linearly.
Local or punching shear
Both equations assume a general shear failure, as in a dense or stiff soil. Where the soil can fail in local or punching shear, AASHTO’s 10.6.3.1.2b reduces its strength, and Rischio applies it by the data in both equations, with no option to pick:
Whether it can is judged by Vesic’s rigidity index of the stratum below the base, with its , and , both the index and its critical value, and the effective stress at :
Below the bearing stratum takes and , and a caution says so. Without that stratum’s and the footing takes general shear, and a note says so.
Two strata
When a weaker stratum lies close enough below the base for the failure to reach it, its strength enters , with no input of its own, by AASHTO’s 10.6.3.1.2d to f in both modes. AASHTO takes “a second layer of soil with different properties affecting shear strength”: a stratum at least as strong as the one above it in every property its strength takes, of the same material, with no lower , (a clay’s ) or , is none. One soil split into strata, at the water table or anywhere else, is no second layer, and neither is a stronger one. Any other stratum below counts by AASHTO’s own test. is the base on its own stratum taken as infinitely thick, and a footing of the same size resting on the lower one’s surface under the soil above it: its depth , its surcharge with the strata’s above it and the water table measured from the ground, its factors the lower stratum’s. Both are by AASHTO’s equation, the one these provisions are written for. That overburden is how Vesic (1975), the source of these equations, takes in his worked example of a sand over a clay, so that a lower stratum right under the base gives the base’s own bearing on it. The lower stratum counts when and it is within the critical depth below the base (Eq. 10.6.3.1.2d-1), and a softer clay under a clay past it too, as below:
With the distance from the base down to the lower stratum:
- Two clays, the softer below (10.6.3.1.2e): , with , the punching index ( for a strip) and . The softer clay counts past too, until reaches its cap , where is the upper clay’s own. AASHTO’s critical depth is Vesic’s (1975), which he derives for an upper layer without cohesion; his equation for two clays bounds at , and his worked example of them checks no critical depth. AASHTO applies the critical depth to every two-layer system; for two clays Rischio lets run past it to its cap, the conservative side. So grows with without a step: a 2 × 2 m footing 1 m deep on a clay of 80 kPa over one of 30 bears 400 kPa with the softer clay 1.24 m below, and 402 kPa at 1.25 m, past , where leaving the softer clay out would give 510 kPa.
- A drained stratum over a weaker one (10.6.3.1.2f, Eq. 10.6.3.1.2f-1):
- A clay over a weaker drained stratum is in neither provision: , the footing on the lower stratum alone, without the clay’s shear above it, the conservative side.
is never more than . With the general equation, the pairing governs only where it gives less than the base’s own by that equation. A warning names the weaker stratum when it governs, and the drawing shows the punched block.
A stronger stratum below only raises , and Rischio doesn’t count it: a stiffer clay below a clay is left out, with a note (Fig. 10.6.3.1.2e-2), and so is a stronger drained stratum. Rock below the strata isn’t counted either; the equations take the soil, the conservative side.
The provisions are for two strata. With more below the base, Rischio pairs the base’s stratum with the next, and each deeper stratum with each one from the base’s down, the soil between taken as that one; the lowest governs, and a note names the strata it took as one. A clay given without its can’t be paired, and the search stops at it, with a warning.
Factor of safety
In free mode the factor of safety weighs against the pressure that loads the soil, against the designer’s limit, with FHWA GEC 6’s 3.0 (§5.2.6) beside it as a reference (Design criteria). With the load centred it is , with . Under an eccentric load it is , with the equivalent uniform pressure on the effective area, ( per metre of a strip), as UFS 3-220-20 (§4-5.1.4) and FHWA NHI-06-089 (Fig. 10-17, after NAVFAC 1986b) put it for a base on soil: the soil yields under the most loaded edge and the failure takes the whole effective area, which already counts through and . Weighing it against would count the eccentricity twice.
Results also gives the net ultimate capacity, what’s left once the overburden the soil already carried before the excavation is taken away, , the way deep footings are often judged; the check uses the gross . Where a weaker stratum governs, the base’s own on its stratum is beside it too.
Under AASHTO the check is against the factored pressure on the effective area, with the code’s resistance factor (AASHTO LRFD). A wall’s base is checked the same way, in Retaining walls › Bearing capacity.
Sliding
A horizontal load pushes the footing along the stratum its base rests on. In free mode the check is , the same method as a wall’s sliding: AASHTO’s 10.6.3.4, its rule taken from the data, on the whole base (per metre of a strip; a circle as the square of its area):
- On a drained soil, friction, concrete cast against it: . Its isn’t counted.
- On a clay, its undrained strength over the base: .
- On a drained stratum over a clay: with at least 0.15 m of it below the base, AASHTO’s 6 in. of granular material, the area under the lesser of and half the normal stress across the base (AASHTO’s figure 10.6.3.4-1), ; thinner, the clay’s . The base takes the lesser of this and its friction. The normal stress varies linearly across the base with the load’s eccentricity, a plane under moments both ways, and is zero where the base lifts off: holds where passes , half the stress elsewhere. A centred load gives ; an eccentric one, less.
The soil in front of an embedded footing isn’t counted, the safe side, and the check’s trace says so. The designer’s limit judges it, with FHWA GEC 6’s 1.5 (§5.4) beside it as a reference. Under AASHTO it’s against the factored horizontal load, with the code’s (AASHTO LRFD).