Bearing capacity
Eccentricity and effective area, linear contact pressure, the general bearing capacity equation with every factor, and the factor of safety of a footing.
This page follows the load from where it acts on the base to the factor of safety; the units, conventions and assumptions are in Method and assumptions.
Eccentricity and effective area
The moments move the resultant off centre by and . The bearing capacity uses Meyerhof’s effective area, the part of the base centred on the resultant. Its sides are and : is the shorter of them and the longer, whichever the user called the width. A strip has only . The shape factors use and the term uses , while the depth factors and the zone that sets use the shorter side of the base, .
Contact pressure
The contact pressure is linear over the whole base, with and at opposite corners (at the edges, for a strip) and , or per metre for a strip. Once exceeds 1, is negative: that corner would be in tension, which the soil can’t take, so it lifts off. Rischio doesn’t redistribute the pressure; it keeps the negative value to show how far out the load is. With one eccentricity this is the middle third: or makes negative and fails its eccentricity check.
When or the resultant falls outside the base and the footing overturns: there is no contact pressure or , and the bearing check fails with .
Ultimate bearing capacity
comes from the general bearing capacity equation (Meyerhof), with the factors as Das & Sivakugan give them and the and of the bearing stratum. The base of a retaining wall takes it from the same equation, as a strip:
The overburden is the effective vertical stress at the base: the weight of the strata above, with above the water table and below, less the pore pressure. is the thickness-weighted average between and , with above the water table and below. With one stratum these are the textbook’s three cases: the water table above the base, within below it, or deeper.
Bearing capacity factors
Reissner, Prandtl and Vesic; with , the undrained case, , and :
Shape factors
De Beer’s, with the effective dimensions and ; for a strip and all three are 1:
Depth factors
Hansen’s, with the full width , the shorter side of the base, for :
With , and . For , is replaced by , in radians.
Inclination factors
Meyerhof’s, and Hanna and Meyerhof’s, with the inclination of the load in degrees, the same whichever way the load leans. Once the term is gone, (the square would bring it back); with , :
Factor of safety
The factor of safety is , against 3.0 by default. An eccentric load enters both terms: through and , and through the moments.